What a 5 kW inverter actually carries
A 5 kW continuous output covers a normal house most of the day: fridge and freezer, lights, router and office gear, a washing machine, a microwave, a TV. What it does not cover is everything at once. Add up the nameplate watts of the loads that run together, then apply four rules.
- Continuous versus surge. Motors start at three to six times their running watts. A 1.1 kW well pump can pull 4–6 kW for a second, which is most of a 5 kW budget on its own.
- Air conditioning. A 3.5 kW split unit draws about 1.2 kW running but 3–4 kW at startup, and a heat pump is worse in cold weather.
- Dryers and ovens. An induction hob plus a heat-pump dryer is 4–6 kW steady. Run them in daylight on solar rather than at 8 pm on battery.
- Water heating. A 3 kW element plus a kettle plus a microwave is already past 5 kW. Most nuisance trips on a 5 kW system trace back to a water heater.
Why 48 V almost always comes with 5 kW
At 5 kW a 48 V bank carries about 104 A, a 24 V bank about 208 A and a 12 V bank about 417 A. Current decides cable size, breaker rating and heat, so 48 V is the practical floor above roughly 3 kW. If a 5 kW unit you are considering is specified for 12 V or 24 V, it is aimed at vehicles and cabins, not at a house.
Single phase, split phase, three phase
Most 5 kW residential units are single-phase 230 V. In North America you also meet 5 kW split-phase (120/240 V) models: check that the unit supplies both legs, because a 240 V well pump and 120 V circuits usually have to coexist. Three-phase 5 kW exists but is rare outside 400 V European markets.
What array size to pair with it
A DC/AC ratio of 1.2–1.35 is normal, so 6–6.8 kW of panels. Yield depends on location: at about 4.2 peak sun hours a 5 kW inverter produces roughly 18–21 kWh on a clear day, and closer to 13–15 kWh in the Northeast or the Pacific Northwest. Pair it with 10–15 kWh of battery for overnight essentials rather than for the whole house.
Where 5 kW is the wrong size
- All-electric house with a heat pump, EV charger and induction cooking: start at 8–10 kW.
- Cabin or van: 2–3 kW is enough and the smaller unit has lower idle draw.
- Adding an EV later: size up now. An 11 kW charger on a 5 kW inverter means the car can only charge from the grid or at a reduced rate.
What to put on the quote request
Continuous and surge output, phase and output voltage, battery voltage window, charger current, idle draw, and whether the unit is grid-interactive or off-grid only. With those six numbers two 5 kW inverters can be compared in minutes, and the surprise usually disappears before the money does. If you already know your bank voltage, the 48 V page covers cable and breaker sizing in detail.