What off grid changes about the inverter
An off grid system has no utility to fall back on, so the inverter carries every load, every start and every mistake. That shifts the specification away from efficiency and toward surge capacity, charger current and idle draw. A unit that scores 97% on a datasheet but cannot start a 1 HP well pump is useless on a site with a pump.
Continuous and surge: the two numbers that matter
Continuous rating is what the inverter can supply indefinitely at the ambient temperature on site, which is often 40 °C in a shed, not 25 °C in a lab. Surge is the short-term overload that starts motors; a well pump or an air compressor can ask for two to three times its running watts for a few seconds.
A simple method:
- List every load and its running watts.
- Add the loads likely to run together — fridge, lights, router, well pump, tools.
- Add the starting watts of the largest motor once.
- Add 20–25% headroom for ageing batteries and hot days.
The result is the number to shop with, and it is nearly always larger than the kW on the sticker.
Battery voltage and charger current
The battery bank sets the DC voltage, and the voltage sets the current for a given power. At 3 kW, a 24 V bank carries about 125 A of DC current; a 48 V bank carries about 62 A. Lower current means thinner cable, smaller breakers and less heat, which is why 48 V is standard above roughly 3 kW and 12 V survives only in cabins.
Charger current matters as much as the inverter output in an off grid system: it determines how fast the array refills the bank after a cloudy day. Plan for a charger that can deliver roughly 10–20% of the bank's amp-hour capacity, and check the maximum PV input the unit accepts — a charger capped at 4 kW will clip a 6 kW array for much of the year.
Low frequency vs high frequency
Low-frequency units use a large iron transformer and weigh 20–40 kg or more. They tolerate surge, start motors and survive heat better, and they are the usual choice for pumps, workshops and full-time off grid houses. High-frequency units are lighter, cheaper and more efficient at part load, but their surge headroom is smaller.
Wiring basics
- Cable size follows current and run length; a long DC run from the array costs more in copper than the difference between two inverter models.
- Put a DC breaker between the battery bank and the inverter, rated for the continuous current plus a margin.
- Ground the enclosure and the array frame to a single point, and bond the battery bank negative according to the local code.
- Keep the inverter in a ventilated space; derating begins well before the case feels hot.
Matching the array to the bank
An off grid array only delivers what the battery can absorb. If the bank is 48 V 200 Ah (about 9.6 kWh nominal), an array much above 3–4 kW will spend the middle of sunny days at absorption voltage with nowhere to put the energy. Buy panels after you have sized the bank, not before.
When the site also has a grid connection or a generator that should charge the bank, a hybrid unit usually does the same job with a smaller parts count — see the hybrid and 48V guides.