The method, in five steps
1. List every load and its running watts. Use the nameplate figure, or a plug-in energy meter reading at the wall. A fridge says 150 W, a router 10 W, a TV 80 W, a kettle 2,400 W.
2. Decide what runs at the same time. This is where most people over- and under-size at once: they add every appliance in the house, then forget that the pump starts while the microwave is on.
3. Convert VA to W if the label is in VA. Multiply apparent power by the power factor: 1,500 VA at 0.8 is 1,200 W. Inverters are rated in W (good ones also state a power factor), so compare in W.
4. Add the surge of the largest motor. Compressors and pumps draw 2–3× their running watts for a second or two. A 750 W pump needs about 2,250 W of surge headroom on top of everything else running.
5. Add 25% headroom. Inverters are most efficient and coolest in the 30–70% load band; running one at 100% continuously is how you buy two inverters.
Three worked examples
Cabin, weekend use. Lights 100 W, fridge 150 W, laptop and router 100 W, small pump 500 W running (1,500 W start). Continuous: 850 W. Plus surge and headroom: a 2–3 kW unit covers it, and 24 V is common in this class.
Small house with a well. Fridge 200 W, lights and electronics 400 W, microwave 1,200 W, well pump 750 W (2,250 W start), washing machine 500 W. Continuous sum: about 3,050 W, but not all at once — apply diversity and the realistic peak is 2,200–2,500 W, plus a pump start. A 3–5 kW unit at 48 V fits.
All-electric house. Heat pump, induction hob, oven, water heater: continuous peaks of 8–12 kW. A 10 kW hybrid covers backup circuits, not the whole panel, unless the loads are managed.
Grid-tie is sized differently
On a grid-tie system the inverter is sized against the array, not the loads, because the house draws from the grid when the array cannot keep up. The common rule is a DC/AC ratio of about 1.1–1.3, so a 6 kW array pairs with a 4–5 kW inverter. Higher ratios clip production in summer but produce more in winter and at low light.
Battery-side check: the number most people skip
Once the inverter size is chosen, convert it back to DC current:
- 3,000 W at 48 V ≈ 63 A before losses, about 69 A at 90% efficiency.
- 5,000 W at 48 V ≈ 104 A, about 116 A at 90%.
- 8,000 W at 48 V ≈ 167 A, about 185 A at 90%.
Cable, fuse and battery must all carry that current. A correctly sized inverter on an undersized battery does not trip the inverter — it collapses the battery voltage and resets everything.
Mistakes that change the answer
- Sizing on watts only and ignoring which loads start at the same moment.
- Forgetting that the continuous rating is quoted at 25 °C.
- Choosing 12 V above 2 kW: 2,500 W at 12 V is over 200 A.
- Sizing the inverter bigger than the battery can feed.
- Ignoring idle draw, which runs 24 hours a day and is invisible in the sizing maths.
The short version
Add the loads that run together, add the largest motor's start current, add 25%, then choose the battery voltage that keeps DC current under about 150 A. That gives a number, and the number usually lands on a standard size: 1 kVA for a cabin, 3 kVA for a small house, 5 kVA for a house with a well and a microwave, 10 kVA for managed whole-house backup.