What size inverter do I need? Size it from loads, not guesses

The right size comes from three numbers: what runs at the same time, what the biggest motor draws when it starts, and how much DC current your battery can actually deliver. Everything else is a standard size you round to.

PV array 200–500 V DC Battery 48 V nominal House 120 / 230 V AC Grid or genset MPPT DC → AC Transfer relay 1 2 3 4 5

Anatomy

Five connections decide which model fits. Ask for the datasheet to confirm each one on the exact rating you are buying.

  1. 1PV DC inputString voltage window and max input current per tracker.
  2. 2MPPT trackerOne tracker per roof orientation; two trackers help a partly shaded array.
  3. 3Battery portNominal voltage and chemistry must match the bank you already own.
  4. 4AC outputContinuous and surge rating, and whether the backup panel is separate.
  5. 5Grid or genset inputGrid-code approval for your country, plus generator start support.

The method, in five steps

1. List every load and its running watts. Use the nameplate figure, or a plug-in energy meter reading at the wall. A fridge says 150 W, a router 10 W, a TV 80 W, a kettle 2,400 W.

2. Decide what runs at the same time. This is where most people over- and under-size at once: they add every appliance in the house, then forget that the pump starts while the microwave is on.

3. Convert VA to W if the label is in VA. Multiply apparent power by the power factor: 1,500 VA at 0.8 is 1,200 W. Inverters are rated in W (good ones also state a power factor), so compare in W.

4. Add the surge of the largest motor. Compressors and pumps draw 2–3× their running watts for a second or two. A 750 W pump needs about 2,250 W of surge headroom on top of everything else running.

5. Add 25% headroom. Inverters are most efficient and coolest in the 30–70% load band; running one at 100% continuously is how you buy two inverters.

Three worked examples

Cabin, weekend use. Lights 100 W, fridge 150 W, laptop and router 100 W, small pump 500 W running (1,500 W start). Continuous: 850 W. Plus surge and headroom: a 2–3 kW unit covers it, and 24 V is common in this class.

Small house with a well. Fridge 200 W, lights and electronics 400 W, microwave 1,200 W, well pump 750 W (2,250 W start), washing machine 500 W. Continuous sum: about 3,050 W, but not all at once — apply diversity and the realistic peak is 2,200–2,500 W, plus a pump start. A 3–5 kW unit at 48 V fits.

All-electric house. Heat pump, induction hob, oven, water heater: continuous peaks of 8–12 kW. A 10 kW hybrid covers backup circuits, not the whole panel, unless the loads are managed.

Grid-tie is sized differently

On a grid-tie system the inverter is sized against the array, not the loads, because the house draws from the grid when the array cannot keep up. The common rule is a DC/AC ratio of about 1.1–1.3, so a 6 kW array pairs with a 4–5 kW inverter. Higher ratios clip production in summer but produce more in winter and at low light.

Battery-side check: the number most people skip

Once the inverter size is chosen, convert it back to DC current:

  • 3,000 W at 48 V ≈ 63 A before losses, about 69 A at 90% efficiency.
  • 5,000 W at 48 V ≈ 104 A, about 116 A at 90%.
  • 8,000 W at 48 V ≈ 167 A, about 185 A at 90%.

Cable, fuse and battery must all carry that current. A correctly sized inverter on an undersized battery does not trip the inverter — it collapses the battery voltage and resets everything.

Mistakes that change the answer

  1. Sizing on watts only and ignoring which loads start at the same moment.
  2. Forgetting that the continuous rating is quoted at 25 °C.
  3. Choosing 12 V above 2 kW: 2,500 W at 12 V is over 200 A.
  4. Sizing the inverter bigger than the battery can feed.
  5. Ignoring idle draw, which runs 24 hours a day and is invisible in the sizing maths.

The short version

Add the loads that run together, add the largest motor's start current, add 25%, then choose the battery voltage that keeps DC current under about 150 A. That gives a number, and the number usually lands on a standard size: 1 kVA for a cabin, 3 kVA for a small house, 5 kVA for a house with a well and a microwave, 10 kVA for managed whole-house backup.

FAQ

Common questions

How do I calculate what size inverter I need?

Add the running watts of everything that runs at the same time, add the start current of the largest motor (2–3× its rating for a second), then add 25% headroom. Choose the battery voltage that keeps DC current under about 150 A.

What size inverter do I need for a house?

For a normal house with a fridge, lights, electronics and a microwave, 3–5 kW covers the essentials. Add an electric hob, oven or water heater and the figure climbs past 8 kW, which is usually solved with load management rather than a bigger inverter.

What is the difference between 3 kW and 5 kW inverter sizing?

Three kW at 48 V is about 63 A before losses; at 24 V it is about 125 A. Above roughly 3 kW, 48 V is the practical choice because it halves the current for the same load, so cable, fuses and terminals stay manageable.

Should the inverter be sized to the panels or to the loads?

On a grid-tie system the inverter is sized against the array, usually with a DC/AC ratio of about 1.1–1.3. On off-grid and hybrid systems it is sized against the loads and the battery's ability to deliver the current.