The two outages people actually have
Most residential outages fall into two shapes. Short ones — a few minutes to a few hours, several times a year, from storms, trees and grid faults. And long ones — a day to a week, after a hurricane, an ice storm or a wildfire shut-off.
An inverter with a battery is excellent at the first shape and adequate at the second only if something recharges it. A generator is clumsy at the first shape and made for the second. Buying the wrong one for your outage shape is the most common mistake in backup power.
Startup: milliseconds versus seconds
A hybrid inverter with backup output switches in under 20 ms, which most electronics do not notice; a UPS-grade unit keeps desktop machines and NAS drives running. A home standby generator takes about 10–30 seconds to start and transfer, and a portable unit has to be started and plugged in by hand. That ten-second gap is why fridges and freezers are fine on either, but servers, medical equipment and anything mid-write are not.
Runtime: hours versus days
A battery's runtime is arithmetic: usable kWh divided by load. A 10 kWh battery with 8 kWh usable carries 500 W of essentials for about 16 hours, or a 2 kW well pump plus a fridge for under three. When the battery is empty, it stays empty until the sun or the grid comes back.
A generator's runtime is fuel. A 5 kW portable unit at half load typically burns one and a half to two and a half litres per hour and needs refuelling every 6–10 hours, which means storing fuel safely and going out in the storm. Long outages expose the real constraint: fuel, not hardware.
Noise and where you can run it
A generator at 60–70 dB at seven metres is a conversation-stopper, and in a suburban lot it is also a neighbour problem, which several jurisdictions regulate by hours. Battery inverters run at 30–45 dB — a fan, not an engine — and can live in a garage or utility room. Noise is often the reason people choose the expensive option.
Output quality
Conventional generators produce 5–15% total harmonic distortion, and cheaper units drift in frequency under changing load. Heat pumps, variable-speed compressors and some power supplies age faster on that. Inverter generators and hybrid inverters clean the incoming AC to under about 3% THD, which is why installers increasingly pair a generator with a hybrid inverter instead of using the generator alone.
The combination most installers fit
A hybrid inverter with backup output plus a battery plus a generator input. The inverter runs the house silently for short outages, the generator is started only for long ones, and it recharges the battery at the same time instead of carrying the load directly. You get instant transfer, clean power, days of runtime, and the generator runs a few hours a day rather than around the clock.
What decides it for your house
- Outage length. Under a day: battery and inverter. Multiple days: generator, or both.
- Critical loads. A fridge, lights, router and a well pump fit in 2–3 kW; a heat pump does not.
- Recharge path. Solar, grid, or generator — one of the three has to be in the plan.
- Site constraints. Fuel storage, noise rules, carbon monoxide, where the unit can sit.
Answer those four and the choice stops being about brands and starts being about arithmetic. If solar is part of the plan, the hybrid page describes how the inverter switches between grid, battery and generator input without a manual transfer switch.