What 3,000 W actually runs
Start from running watts, not from the panel count. Typical figures for a house or cabin:
- Fridge or freezer: 100–200 W running, 500–800 W for a second or two at compressor start.
- Well or booster pump: 750–1,100 W running, 2–3× that at start.
- Microwave: 1,000–1,500 W while it runs.
- Induction hob: 1,800–2,000 W per zone at full power.
- Kettle: 2,000–3,000 W, briefly.
- Lights, router, laptops, TV: 150–400 W together.
A 3 kW inverter carries the fridge, lights, TV, router and one pump comfortably. It carries a kettle or a hob, but not both with the pump starting. That is the whole sizing question in one sentence.
Continuous, surge, and why 3 kW is not always 3 kW
Three numbers hide behind the rating:
- Continuous rating, usually quoted at 25 °C. Above 40 °C ambient most units derate, and a closed cabinet in summer reaches that easily.
- Surge rating, given for 5–20 seconds. Motor starting is what needs it: a 750 W pump can pull 2,250 W for a moment.
- Apparent power. A load rated in VA draws amperes according to its power factor. A 3 kW unit rated at power factor 0.8 is 3.75 kVA, and a load with a poor power factor uses that headroom up faster than its watt figure suggests.
24 V or 48 V: the current decides the cable
Current is watts divided by volts, before losses:
- 3,000 W at 24 V: 125 A. At 90% efficiency, about 139 A.
- 3,000 W at 48 V: 62.5 A. At 90% efficiency, about 69 A.
That is why 48 V took over above roughly 3 kW. Halving the current halves the cable cross-section for the same loss, and it makes fuses, breakers and terminals cheaper and cooler. Keep the DC run short — ideally under two metres — and fuse at the battery, not at the inverter.
The three 3 kW products that share the name
- Off-grid inverter/charger. DC input from a battery, AC output to the house, plus a charger for a generator. No grid interaction at all.
- Hybrid. Grid input, battery port, PV input and a backup output. The right choice when the utility exists and you want both.
- Grid-tie. No battery, DC from the array, AC synchronised to the grid, and it shuts down when the grid drops. A 3 kW grid-tie unit is a different product from a 3 kW off-grid unit, not a setting.
What to check before you order
- Continuous rating at your ambient temperature, not at 25 °C.
- Surge wattage and its duration — 5 seconds is not enough for a deep-well pump.
- Idle draw, because it runs 24 hours a day and eats 0.4–1 kWh daily at 15–40 W.
- Charger amperes if a generator will be connected.
- Transfer time, if computers are on the backup output.
- Grid-code certification for the country of installation, on the exact model.
Four mistakes that show up in every 3 kW retrofit
- Buying by price and discovering the continuous rating is quoted at 25 °C with a 30-minute limit.
- Putting a 3 kW inverter on a 12 V bank: that is 250 A before losses, and most 12 V systems cannot start a pump without the voltage collapsing.
- Sizing the inverter but not the battery: a 3 kW load empties a 5 kWh battery in under two hours.
- Forgetting the well pump's start current, then blaming the inverter when it trips on a hot afternoon.